Home / News & Resources / FAQs / There are seven points to know when laying the gas tracer wire

There are seven points to know when laying the gas tracer wire

Source: Hengtong Electric Published: 2022-06-24 0 views
Because the PE pipe is non-conductive and non-magnetic, it is impossible to track the PE pipe, which brings inconvenience to the future pipeline maintenance. The gas tracer wire effectively solves the problem that non-metallic pipelines cannot be detected by metal pipeline detectors. So what are the precautions for laying the trace line?
1. When laying, it shall be in a straight line close to the PE pipe and be located on the top surface of the pipe. Do not bury the PE pipe in spiral shape, which may lead to inaccurate test results.
2. A certain length of conductor (more than 1m) shall be reserved for the tracer wire at the manhole or outside the ground for signal detection and application. This can improve the detection efficiency and accuracy.
3. The tracer wire joint or branch point must be firmly connected to maintain good conductivity and wrapped with insulating tape to prevent corrosion and disconnection caused by underground moisture and interrupt the detection signal. The tracer wire at the steel plastic conversion joint of the pipeline can be welded on the flange, and the joint shall be subject to anti-corrosion treatment to prevent disconnection due to long-term corrosion.
4. In order to increase the signal strength of the tracer wire and make the signal distribution uniform, the grounding resistance at the buried end of the tracer wire must be reduced as much as possible during construction, and the grounding measures of peeling off the skin shall be taken. The insulation layer of exposed core wire shall be 30 cm. In particular, the end of the branch pipe with short length must be well grounded, otherwise the signal on the branch pipe will be very weak and can not be detected.
Gas Pipeline Tracer Wire
5. If the buried length of the pipeline exceeds 1 km, and there is no manhole and other facilities to reserve a tracer head to meet the detection needs, it is recommended to set a test pile every kilometer and reserve a tracer for joint detection.
6. During the construction of trenchless engineering, the tracer wire outside the PE pipe is easy to be broken during the pipe dragging process. The simple method is to select steel wire or wire rope with larger cross-sectional area and higher strength, or use it inside the pipeline. Pre threading the tracer wire can avoid disconnection, and the detection effect is the same as that of the outside, but the connection between the inner tracer wire and the outer tracer wire needs to be handled well.
7. In some special cases, the gas tracer wire cannot be applied to PE pipes. At this time, the method of embedding tracer balls can be used to meet the needs of future detection and positioning.
The above is the relevant content of the question answer. I hope it can help you. If you still have any questions about this problem, you are welcome to follow our website http://webtest2.daoshangbao.cn And consult our staff, will serve you wholeheartedly.