Welcome to Hengtong Electric

Industry News
Home / News & Resources / Industry News / What lists should be paid attention to in the list of gas tracers

What lists should be paid attention to in the list of gas tracers

Source: Hengtong Electric Published: 2024-01-23 0 views

The "tracer wire" is used for the detection, tracking, and positioning of PE pipelines. The tracer wire is laid together with the PE pipe; Generally, metal wire cores are used to apply signals to the "metal wire" through detection equipment, and the detection receiver receives the signal to find the accurate position of the tracer wire, that is, synchronously tracking the specific position of the PE gas pipeline; To facilitate the renovation and maintenance of PE pipelines.

2, The development of tracer wire

1. The first generation tracer wire is composed of a matrix of aluminum foil and plastic film. The aluminum foil is mainly used for signal transmission, and the matrix is a fixed aluminum foil. The disadvantages of this tracer wire are that the strength of the aluminum foil is very low, and it is easy to break even during production and transportation. The auxiliary equipment is easily damaged, and the resistance of the aluminum foil is very high, which limits the effective detection distance and depth.

2. The second generation tracer wire is made by pressing steel wire and plastic film. The tracer wire is made of steel wire as the conductor, with high resistance and limited detection distance, making it difficult to meet practical needs.

3. The third generation tracer wire is composed of a copper clad steel metal wire core and a PE outer protective layer, with a linear appearance.

20220923112016525.jpg

3, Precautions for laying tracer wire

1. When burying the tracer wire, it should be closely attached to the PE pipeline in a straight line shape and located on the top surface of the pipeline. Do not bury the PE pipeline in a spiral shape, as this can lead to inaccurate detection results.

2. A certain length of wire (1m or more is recommended) should be reserved for the tracer wire in the inspection well or at the exit of the ground, for the purpose of detecting and applying signals. This can improve detection efficiency and accuracy.

3. The connector or branch point of the tracer wire must be firmly connected, maintain good conductivity, and wrapped with insulating tape to prevent corrosion and wire breakage caused by underground moisture, which may interrupt the detection signal. The tracer wire at the steel plastic conversion joint of the pipeline can be welded to the flange, and the joint should be treated with anti-corrosion measures to prevent corrosion and breakage over time.

4. To increase the signal strength of the tracer wire and ensure even signal distribution, it is necessary to minimize the grounding resistance at the buried end of the tracer wire during construction, and take good grounding measures by peeling off the insulation layer and exposing the core wire 30 cm. Especially for the ends of shorter branch pipes, they must be well grounded, otherwise the signal on the branch will be very weak and cannot be detected.

5. If the buried length of the pipeline exceeds 1 km and there are no inspection wells or other facilities in the middle to reserve tracer heads for detection needs, it is recommended to install a test pile at each kilometer and reserve tracer wire joints for use during detection.

6. In non excavation engineering construction, the tracer wire outside the PE pipeline is prone to breakage during the dragging process. A simple method is to choose a larger cross-sectional area and higher strength wire or steel wire rope, or pre thread a tracer wire inside the pipeline to avoid breakage. The detection effect is the same as on the outside, but when doing so, it is necessary to handle the problem of connecting the internal tracer wire head to the external tracer wire.

7. In some special cases, it is not possible to apply tracer wire to PE pipelines. In such cases, the method of embedding tracer balls can be used to meet future detection and positioning needs.

This article is supported by pipeline tracing technology. For more detailed and exciting content, please click on our website http://webtest2.daoshangbao.cn We will wholeheartedly provide you with satisfactory service.