Problems needing attention in the installation of tracer wire in PE pipeline
During the operation and handover of PE pipes, there are 5 items to check the compliance of tracer wire:
① Check whether the signal access point exists and is installed correctly.
② The detection signal can be loaded on the tracer wire. There are too many intermediate faults and serious leakage. There is no detection well in the middle.
③ The tracer wire shall be installed with the head and tail cut off and suspended in the air, not in contact with the ground, and the tracer wire of the middle valve well shall not be fixed.
④ The diameter of the tracer wire is too small to meet the requirements of detection signal transmission, and it is easy to be cut off by construction or damaged by natural stress.
⑤ PE pipe surface signs are buried according to the installation memory impression, with insufficient density and large deviation.
The continuity and smoothness of the detection signal cannot be guaranteed. There are five main reasons:
① The lead in the tracer is not connected properly, resulting in an open circuit.
② The tracer wire is not insulated and waterproof, resulting in signal short circuit.
③ The conductive area of the metal wire is not enough, resulting in large signal transmission resistance and large signal attenuation.
④ The tracer wire itself is unqualified and the broken wire is discontinuous.
⑤ The head end of the tracer wire is not connected, fixed, grounded, cut or buried, and the head cannot be found.
No exposed probe signal source.

The PE pipe tracer wire is designed without signal contact or is not installed according to the contact design. Many units directly bury the tracer wire connector under the ground or directly wrap the tracer wire connector on the pipeline or equipment when installing the tracer wire. In a short time, the tracer joint will not be found, resulting in the whole tracer becoming useless.
The area is too small and the strength is not enough.
Incorrect selection of wire cross-sectional area. Before selecting a trace line, it is necessary to determine which detector to use. Different detectors have different detection principles and methods, so it is necessary to select a targeted tracer wire. The type and cross-sectional area of wire shall be selected according to the signal strength of detector signal generator and the detection distance required for pipeline design. Generally, the one-time detection distance of 2.5mm2 copper core wire can reach 500~1000m. The direct method will be further away, and there will be little tension and fracture during construction.
Replace the pipe trace line with warning tape. The tracer wire was replaced by warning tape and was not laid according to the standard requirements.
The above is the relevant content of the question answer. I hope it can help you. If you still have any questions about this problem, you are welcome to follow our website http://webtest2.daoshangbao.cn And consult our staff, will serve you wholeheartedly.